跳到主要导航 跳到搜索 跳到主要内容

Experimental investigation of an ejector-enhanced auto-cascade refrigeration system

  • Xi'an Jiaotong University

科研成果: 期刊稿件 › 文章 › 同行评审

81 引用 (Scopus)

摘要

This study presents the experimental investigation of an ejector-enhanced auto-cascade refrigeration cycle (EARC) with zeotropic refrigerant R134a/R23. Performance comparisons among the EARC and two conventional cycles were conducted at selected operating conditions. The effects of ambient temperature, charged mass fraction ratio of the mixture, throttle valve opening, and heat load on the performance characteristics of the EARC were investigated. The results indicated that the EARC had more advantages in terms of lower refrigeration temperature and higher energy utilization efficiency over the conventional cycles, and the coefficient of performance (COP) and exergy efficiency improvements of the EARC reached up to 9.6% and 25.1%, respectively. The throttle valve opening was optimal with respect to the maximum system exergy efficiency determination. The refrigerant R134a/R23 with the optimal mass fraction ratio of 0.70/0.30 was proposed.

源语言英语
页(从-至)792-801
页数10
期刊Applied Thermal Engineering
卷129
DOI
出版状态已出版 - 25 1月 2018

学术指纹

探究 'Experimental investigation of an ejector-enhanced auto-cascade refrigeration system' 的科研主题。它们共同构成独一无二的学术指纹。

引用此