Experimental investigation of a data server cabinet integrated with an indirect evaporative plate falling film heat exchanger: Heat transfer enhancement and cabinet-level cooling energy savings

  • Ganglin Cao
  • , Shuzhi Zhang
  • , Guoqiang Liu
  • , Zhiru Li
  • , Yulong Sun
  • , Yani Pang
  • , Rong Feng
  • , Hong Cui
  • , Weizhi Tian
  • , Hongliang Chang
  • , Xiongwen Zhang
  • Shaanxi University of Technology
  • Xi'an Jiaotong University
  • Northeast Electric Power University

科研成果: 期刊稿件 › 文章 › 同行评审

2 引用 (Scopus)

摘要

To investigate a lower-energy cooling approach for a cabinet-scale data server system, this paper proposes and experimentally investigates an innovative cabinet-level cooling architecture that integrates a data server cabinet with an indirect evaporative plate falling film heat exchanger (PFFHE). A precision liquid film distributor capable of precisely metering water admission into the PFFHE, together with a techno-economically optimized PFFHE unit featuring a ‘mortise-tenon’ architecture, is developed. In the experiments, liquid guiding fibers are employed to improve the uniformity of liquid film distribution along the vertical wall of the PFFHE, while the energy consumption associated with liquid film transport is reduced by minimizing the water usage. This study systematically analyzes the effects of different operating conditions on the liquid film flow characteristics, cabinet internal temperature, and air-side heat transfer coefficient (HTC), and further evaluates the influence of cooling modes and rack-mounted load powers on cabinet-level cooling energy performance, including cabinet-level power usage effectiveness (PUE) within the defined experimental boundary. Two key findings are obtained. (1) Compared with standalone air cooling, the air-side HTC achieved by the air-water-liquid guiding fiber cooling mode is 5.61 times greater than that of the air cooling mode; (2) Under the ASHRAE Class A2 allowable inlet temperature constraint (≤35 °C), the supports a maximum experimentally validated rack-mounted load of 2500 W, at which a minimum cabinet-level PUE of 1.11 is achieved. These results indicate that the proposed cabinet integrated cooling architecture can enhance heat transfer and reduce non-IT cooling energy consumption within a single-cabinet laboratory prototype.

源语言英语
期刊论文编号141004
期刊Energy
卷353
DOI
出版状态已出版 - 15 6月 2026

联合国可持续发展目标

此成果有助于实现下列可持续发展目标:

  1. 可持续发展目标 7 - 经济适用的清洁能源
    可持续发展目标 7 经济适用的清洁能源

学术指纹

探究 'Experimental investigation of a data server cabinet integrated with an indirect evaporative plate falling film heat exchanger: Heat transfer enhancement and cabinet-level cooling energy savings' 的科研主题。它们共同构成独一无二的学术指纹。

引用此