TY - GEN
T1 - Effect of void area on PD magnitude uniformity
AU - Wu, Kai
AU - Pan, Cheng
AU - Meng, Yongpeng
AU - Cheng, Yonghong
PY - 2013
Y1 - 2013
N2 - Accumulated surface charges at the interface between solid dielectric and gas, resulting from former discharges plays an important role in the characters of subsequent ones during the partial discharge (PD) sequences. Specifically, it is assumed that variations in PD magnitude are associated with the discharge area. In our previous research, it was found that the diameter of discharge area can reach up to 1.5 mm due to the dielectric barrier. Based on this, different variation degree of discharge area was obtained via changing the void area in this paper. When the size of void was larger (diameter 5.0 mm), streamer could spread freely after it landed on the interface, so the discharge area varied in a large range, leading to the intense fluctuation of discharge magnitude. After the void diameter was reduced to 1.5 mm, the variation range of discharge magnitude is restricted by the void edge. As the void area became much smaller (diameter 0.7 mm), the uniformity of discharge magnitude increased.
AB - Accumulated surface charges at the interface between solid dielectric and gas, resulting from former discharges plays an important role in the characters of subsequent ones during the partial discharge (PD) sequences. Specifically, it is assumed that variations in PD magnitude are associated with the discharge area. In our previous research, it was found that the diameter of discharge area can reach up to 1.5 mm due to the dielectric barrier. Based on this, different variation degree of discharge area was obtained via changing the void area in this paper. When the size of void was larger (diameter 5.0 mm), streamer could spread freely after it landed on the interface, so the discharge area varied in a large range, leading to the intense fluctuation of discharge magnitude. After the void diameter was reduced to 1.5 mm, the variation range of discharge magnitude is restricted by the void edge. As the void area became much smaller (diameter 0.7 mm), the uniformity of discharge magnitude increased.
UR - https://www.scopus.com/pages/publications/84901741239
U2 - 10.1109/CEIDP.2013.6747069
DO - 10.1109/CEIDP.2013.6747069
M3 - 会议稿件
AN - SCOPUS:84901741239
SN - 9781479925964
T3 - Annual Report - Conference on Electrical Insulation and Dielectric Phenomena, CEIDP
SP - 1165
EP - 1168
BT - 2013 Annual Report Conference on Electrical Insulation and Dielectric Phenomena, CEIDP 2013
T2 - 2013 IEEE Conference on Electrical Insulation and Dielectric Phenomena, CEIDP 2013
Y2 - 20 October 2013 through 23 October 2013
ER -