Effect of refrigerant charge and TXV opening on the performance of air-source heat pump water heater

科研成果: 书/报告/会议事项章节会议稿件同行评审

摘要

This paper describes the experiment carried out to analyze the effects of improper refrigerant charge and incorrect TXV (Thermal Expansion Valve) opening on the air-source heat pump water heater using R134A. The performance of the system were measured in combinations of four refrigerant charges of 70%, 85%, 100% and 115% of the optimal value and three TXV opening of 30%, 45% and 60% of full opening at ambient temperature of 20D/15W (dry-bulb temperature/wet-bulb temperature). The results showed that the maximum COP was nearly 33%, 31.9% and 4.4% higher than that of 70%, 85% and 115% of the optimal refrigerant charge at 60% TXV opening, respectively. And it was found that the increase in TXV opening can enhance COP when water temperature exceeded 30°C.

源语言英语
主期刊名Green Building, Materials and Civil Engineering - Proceedings of the 4th International Conference on GreenBuilding, Materials and Civil Engineering, GBMCE 2014
编辑Jimmy C.M. Kao, Wen-Pei Sung, Ran Chen
出版商CRC Press/Balkema
657-661
页数5
ISBN(印刷版)9781138026698
DOI
出版状态已出版 - 2015
活动4th International Conference on Green Building, Materials and Civil Engineering, GBMCE 2014 - Hong Kong, 香港
期限: 21 8月 201422 8月 2014

丛书

姓名Green Building, Materials and Civil Engineering - Proceedings of the 4th International Conference on GreenBuilding, Materials and Civil Engineering, GBMCE 2014

会议

会议4th International Conference on Green Building, Materials and Civil Engineering, GBMCE 2014
国家/地区香港
Hong Kong
时期21/08/1422/08/14

学术指纹

探究 'Effect of refrigerant charge and TXV opening on the performance of air-source heat pump water heater' 的科研主题。它们共同构成独一无二的学术指纹。

引用此