摘要
The very fast transient over-voltage caused by three operation modes of isolating switch of extra-high voltage GIS in a 550 kV substation is investigated. The transformer winding's end to ground VFTO waveforms and the voltage waveforms of transformer winding pies between 0 and 1 are obtained. The over-voltage of making and breaking short cable of transformer, over-voltage of longitudinal calculating point to ground of transformer winding, and winding pies longitudinal VFTO are calculated, respectively. The results show that the maximum gradient voltage of 1 to 3 winding pies will exceed the critical value under the condition where the isolating switch operates in mode 3 and the transformer is charged. Therefore, the operation mode 3 should be avoided.
| 源语言 | 英语 |
|---|---|
| 页(从-至) | 55-58+62 |
| 期刊 | Gaoya Dianqi/High Voltage Apparatus |
| 卷 | 45 |
| 期 | 4 |
| 出版状态 | 已出版 - 2009 |
学术指纹
探究 'Effect of isolating switch operation on very fast transient over-voltage in extra-high voltage GIS' 的科研主题。它们共同构成独一无二的学术指纹。引用此
- APA
- Author
- BIBTEX
- Harvard
- Standard
- RIS
- Vancouver