摘要
In this paper, a series of laboratory experiments are conducted to investigate the effect of momentary small variations in the transformer operating temperature on the dissolved gas analysis (DGA) measurement. With the increased penetration level of renewable energy sources of intermittent characteristics into electricity grids, operating power transformers are expected to experience frequent temperature variations. Sampling transformer oil during such temperature variation leads to inaccurate diagnosis. Experimental results reveal that gas evolution in transformer oil is greatly affected by the small variations in the operating temperature. Such small variation can be a result of the intermittent generation characteristics of renewable energy sources. Hence, false analysis may be reported if oil is sampled during generation or load fluctuation events. Experimental results are explained through chemical equilibrium constant theory, which indicates that dissolved gases reflect the change in aging rate of the transformer oil-paper insulation system. These results suggest a new paradigm for DGA process through correlating measurements with the transformer operating temperature through the generation and load profiles at the instant of oil sampling.
| 源语言 | 英语 |
|---|---|
| 文章编号 | 9515832 |
| 页(从-至) | 1349-1356 |
| 页数 | 8 |
| 期刊 | IEEE Transactions on Dielectrics and Electrical Insulation |
| 卷 | 28 |
| 期 | 4 |
| DOI | |
| 出版状态 | 已出版 - 8月 2021 |
联合国可持续发展目标
此成果有助于实现下列可持续发展目标:
-
可持续发展目标 7 经济适用的清洁能源
学术指纹
探究 'Dissolved Gas Analysis for Power Transformers within Distributed Renewable Generation-Based Systems' 的科研主题。它们共同构成独一无二的指纹。引用此
- APA
- Author
- BIBTEX
- Harvard
- Standard
- RIS
- Vancouver