DC flashover characteristics of epoxy resin insulator with and without fillers under different SF6 gas pressures

  • Sichuan Electric Power Test and Research Institute
  • State Grid Corporation of China
  • Xi'an Jiaotong University

科研成果: 期刊稿件 › 文章 › 同行评审

14 引用 (Scopus)

摘要

Gas insulated transmission line (GIL) can be used to substitute part of overhead transmission line or power cable under special environments to enhance the flexibility of choosing transmission corridor. The key factor impacting the insulation level of GIL is the charge accumulation along the surfaces of support insulators in DC environment. In this paper, a cone-plate electrode assembly is built to simulate the electric field distribution of coaxial cylindrical structure inside the GIL under DC voltage and the impacts of the filler and the shape of epoxy resin insulator under different SF6 pressures in DC environment on its flashover characteristic are researched. Test results show that in DC GIL the epoxy resin insulator using SiO2 as the filler is indicative of the best insulation performance in short-term voltage impressing and long-term voltage withstanding tests. The points, which attentions should be paid to, in the optimization of contour structure of cone-plate electrode assembly based epoxy resin insulator for DC GIL and the method to approximately acquire charging time constant of insulator are proposed.

源语言英语
页(从-至)155-159
页数5
期刊Dianwang Jishu/Power System Technology
卷34
期8
出版状态已出版 - 8月 2010
已对外发布是

学术指纹

探究 'DC flashover characteristics of epoxy resin insulator with and without fillers under different SF6 gas pressures' 的科研主题。它们共同构成独一无二的学术指纹。

引用此