跳到主要导航 跳到搜索 跳到主要内容

Current-breaking test method based on LC source for hybrid HVDC circuit breaker

  • Xiao Ding
  • , Guangfu Tang
  • , Minxiao Han
  • , Chong Gao
  • , Gaoyong Wang
  • North China Electric Power University
  • Global Energy Interconnection Research Institute Co. Ltd., Beijing

科研成果: 期刊稿件文章同行评审

19 引用 (Scopus)

摘要

Current-breaking test is the core part of the operation tests for DC circuit breaker, whose effectiveness is directly related to the verification of the electrical performance of DC circuit breakers. This paper studies the current-breaking test method of hybrid HVDC circuit breaker for MMC-HVDC system, aiming to present the current-breaking test method and test parameters for engineering feasibility. Firstly, based on the analysis of the principle and working condition of hybrid HVDC circuit breaker, we reveal the its stress characteristics; then, on the basis of stress extraction, we present the LC source test circuit and parameters; finally, we verify the accuracy of the simulation circuit and test method through the short-circuit current-breaking test for a 200 kV circuit breaker, whose results can provide reference for the current-breaking test design of hybrid HVDC circuit breaker.

源语言英语
页(从-至)2-8
页数7
期刊Dianli Jianshe/Electric Power Construction
38
8
DOI
出版状态已出版 - 1 8月 2017

联合国可持续发展目标

此成果有助于实现下列可持续发展目标:

  1. 可持续发展目标 7 - 经济适用的清洁能源
    可持续发展目标 7 经济适用的清洁能源

学术指纹

探究 'Current-breaking test method based on LC source for hybrid HVDC circuit breaker' 的科研主题。它们共同构成独一无二的指纹。