摘要
The coastal urban multi-terminal DC (CU-MTDC) is a prospective solution for enhancing the power supply security of the coastal urban power (CUP) grid and integrating the large-scale offshore wind farm. However, the large DC disturbances may significantly impact the CUP power supply security. The existing DC unbalanced power distribution methods are difficult to be applied in the CU-MTDC because of the complicated optimization process and the expansion of the influence range of a DC fault. To solve the above problems, this paper proposes a coordinated control strategy of CU-MTDC under abnormal conditions. First, calculation principles for the active power reference of center coastal urban power (CCUP) grid converters are proposed. Second, a DC unbalanced power coordinated distribution strategy under abnormal conditions is used based on the dynamic priority control to ensure power supply security of the critical AC lines. Third, the controller parameters of CCUP grid converters are calculated. Through a simple control process, the number of the regulation converters is dynamically scheduled according to the DC unbalanced power. The DC fault influence range on the urban power grid can be limited in a sufficiently small area. Simulation verified the effectiveness of the proposed control strategy.