摘要
;The combination of heat pump and energy storage is an effECtive means to solve the problem of power grid. A simulation platform for air source heat pump coupled phase change thermal storage heating system was built based on TRNSYS, and a new phase change tank module was established and the model was verified by the experimental data. The single factor experiment method was used to explore the influence of the change of system capacity configuration parameters on the system EConomy and energy consumption. The results show that the C0P of the coupled system is 13.8% higher than that of the traditional system. The operation strategy based on the demand response makes the energy saving rate of the coupling system reach 15. 68%. A multi-objECtive optimization function was established with CLC and EC as targets to optimize the configuration parameters. The optimization results show that when the mass of phase change material is 195 kg, the temperature of phase change is 49. 5 C, and the volume of water tank is 1 m-3 the optimization requirements of EConomy and energy saving can be balanced. The results provide guidance for the design requirements of different air source heat pump coupled energy storage systems.
| 源语言 | 英语 |
|---|---|
| 页(从-至) | 84-90 |
| 页数 | 7 |
| 期刊 | Huaxue Gongcheng/Chemical Engineering (China) |
| 卷 | 51 |
| 期 | 11 |
| DOI | |
| 出版状态 | 已出版 - 11月 2023 |
联合国可持续发展目标
此成果有助于实现下列可持续发展目标:
-
可持续发展目标 7 经济适用的清洁能源
学术指纹
探究 'Capacity allocation optimization of coupled phase change energy storage system of air source heat pump' 的科研主题。它们共同构成独一无二的学术指纹。引用此
- APA
- Author
- BIBTEX
- Harvard
- Standard
- RIS
- Vancouver