摘要
A method for calculating the zero-sequence mutual inductance of multi-circuit parallel transmission line on the same tower is proposed. It is pointed out that, the zero-sequence mutual inductance matrix is a set of independent parameters, based on which, the zero-sequence parameters of transmission line in different operation modes can be deduced by matrix transformation. Without the repeating experimental measurement, the proposed method simplifies significantly the acquisition of zero-sequence mutual inductance, which improves the work efficiency. Results of field test for a four-circuit parallel transmission line show its correctness and accuracy.
| 源语言 | 英语 |
|---|---|
| 页(从-至) | 94-99 |
| 页数 | 6 |
| 期刊 | Dianli Zidonghua Shebei/Electric Power Automation Equipment |
| 卷 | 33 |
| 期 | 6 |
| DOI | |
| 出版状态 | 已出版 - 6月 2013 |
| 已对外发布 | 是 |