跳到主要导航 跳到搜索 跳到主要内容

Cable commissioning and diagnostic tests: The effect of voltage supply frequency on partial discharge behavior

  • Xianyong Feng
  • , Qing Xiong
  • , Angelo Gattozzi
  • , Gian Carlo Montanari
  • , Paolo Seri
  • , Robert Hebner
  • University of Texas at Austin
  • University of Bologna

科研成果: 书/报告/会议事项章节 › 会议稿件 › 同行评审

19 引用 (Scopus)

摘要

CIGRE documents, IEEE and IEC standards permit alternate power supply frequencies to reduce the size of the power supply for offline tests, such as those using resonant systems, Very Low Frequency (VLF) and Damped Alternating Current (DAC). To provide insight into the risks of adopting these alternatives, partial discharge (PD) measurements are reported herein for medium voltage (MV) cables with artificial defects, in a range of supply frequencies from 0.01 Hz to 60 Hz and at different temperatures. The results show that varying temperature and frequency changes the PD repetition rate, amplitude and energy, raising questions about the interpretation of diagnostic measurements made at VLF and any other alternate method allowed by the standard.

源语言英语
主期刊名ICPADM 2018 - 12th International Conference on the Properties and Applications of Dielectric Materials
出版商Institute of Electrical and Electronics Engineers Inc.
页373-376
页数4
ISBN(电子版)9781538657881
DOI
出版状态已出版 - 29 6月 2018
活动12th International Conference on the Properties and Applications of Dielectric Materials, ICPADM 2018 - Xi'an, 中国
期限: 20 5月 2018 → 24 5月 2018

丛书

姓名Proceedings of the IEEE International Conference on Properties and Applications of Dielectric Materials
卷2018-May

会议

会议12th International Conference on the Properties and Applications of Dielectric Materials, ICPADM 2018
国家/地区中国
市Xi'an
时期20/05/18 → 24/05/18

学术指纹

探究 'Cable commissioning and diagnostic tests: The effect of voltage supply frequency on partial discharge behavior' 的科研主题。它们共同构成独一无二的学术指纹。

引用此