跳到主要导航 跳到搜索 跳到主要内容

Analysis of power system frequency responses with hydro turbines incorporating load shedding

  • Xi'an Jiaotong University

科研成果: 书/报告/会议事项章节会议稿件同行评审

8 引用 (Scopus)

摘要

As shown in many recent works, the loadfrequency behavior can be represented by system frequency response models especially for an islanding process. In this paper, a frequency response model incorporating an under-frequency load-shedding scheme is presented for islanding power system simulations. The model was applied for a practical power system with both hydro and fossil-fired power generators. The governing system models are involved in the model, which have great impact on the system dynamics. Parameter identification method is used to find and verify the model parameters. Similar responses were observed between the simulations and the accident records. The simulation results showed disadvantages of the primary frequency control systems of hydro power generators at the beginning of the load disturbances. An closed fossil fired power plant is proposed to serve against the load disturbances and improved stability was observed according to the system simulation results.

源语言英语
主期刊名Proceedings of the 2010 5th IEEE Conference on Industrial Electronics and Applications, ICIEA 2010
893-897
页数5
DOI
出版状态已出版 - 2010
活动5th IEEE Conference on Industrial Electronics and Applications, ICIEA 2010 - Taichung, 中国台湾
期限: 15 6月 201017 6月 2010

出版系列

姓名Proceedings of the 2010 5th IEEE Conference on Industrial Electronics and Applications, ICIEA 2010

会议

会议5th IEEE Conference on Industrial Electronics and Applications, ICIEA 2010
国家/地区中国台湾
Taichung
时期15/06/1017/06/10

学术指纹

探究 'Analysis of power system frequency responses with hydro turbines incorporating load shedding' 的科研主题。它们共同构成独一无二的指纹。

引用此