Analysis of beat frequency current amplitude of transmission lines with shunt reactors

  • Gaoyue Zhong
  • , Guobing Song
  • , Huanhuan Wang
  • , Yuanhang Yang
  • , Zhibin Ma
  • Xi'an Jiaotong University

科研成果: 期刊稿件文章同行评审

4 引用 (Scopus)

摘要

At present, researches on the adaptive reclosure lack an analytic expression for beat frequency current about whether the beat frequency current definitely exists and the range of amplitude of the current in adaptive reclosure. The amplitude may be nonexistent or too small when the single-phase transient fault disappears, which will affect the reliability of reclosing determination. The beat frequency current in the shunt reactor is not only affected by sound phase voltage but also by the initial state of components of transmission line when fault disappears. Based on the superposition principle, the complete expression of beat frequency current is obtained, by an analysis of which the minimum beat frequency current and conditions for its occurrence are obtained. It is concluded that the beat frequency current being zero belongs to small probability event. The current is affected by fault time, arc duration, arc resistance, phase angle difference and fault location that make the amplitude obvious. If the amplitude is too small, it will affect the reliability of the reclosing determination. The paper gives the range of amplitude of the beat frequency current on 500 kV transmission lines using the method of the orthogonal experiment in mathematical statistics, proving the beat frequency current can be applied to engineering.

源语言英语
页(从-至)139-145
页数7
期刊Dianli Xitong Zidonghua/Automation of Electric Power Systems
39
11
DOI
出版状态已出版 - 10 6月 2015

学术指纹

探究 'Analysis of beat frequency current amplitude of transmission lines with shunt reactors' 的科研主题。它们共同构成独一无二的学术指纹。

引用此