跳到主要导航 跳到搜索 跳到主要内容

An experimental investigation on capillary pumped loop with the meshes wick

  • Xi'an Jiaotong University

科研成果: 期刊稿件 › 文章 › 同行评审

16 引用 (Scopus)

摘要

A copper-water capillary pumped loop (CPL) is developed for heat recovery applications in the field of the refrigeration and air conditioning. The multi-layer copper meshes are used as the capillary structure in the CPL. The startup characteristics and heat transfer performance of the CPL are investigated experimentally. The experimental results show that for a range of power applied to the evaporator, the system presented reliable startups and continuous operation. The heat transfer performance of the evaporator will be improved if the charging rate of the working fluid or the heat flux is increased properly. The optimal charging rate could be obtained in the range of 70-76% for the given experimental conditions. The study has demonstrated the proposed CPL configuration is able to perform the heat recovery applications.

源语言英语
页(从-至)4503-4507
页数5
期刊International Journal of Heat and Mass Transfer
卷50
期21-22
DOI
出版状态已出版 - 10月 2007

学术指纹

探究 'An experimental investigation on capillary pumped loop with the meshes wick' 的科研主题。它们共同构成独一无二的学术指纹。

引用此