跳到主要导航 跳到搜索 跳到主要内容

An efficient accuracy improvement method for cable defect location based on instantaneous filtering in time-frequency domain

  • Xingyu Zou
  • , Haibao Mu
  • , Renjie Wang
  • , Kaixuan Fan
  • , Ziqian Cheng
  • , Yifan He
  • , Guanjun Zhang
  • Xi'an Jiaotong University
  • State Grid Zhejiang Electric Power Research Institute

科研成果: 期刊稿件文章同行评审

20 引用 (Scopus)

摘要

Time-frequency domain reflectometry is a highly sensitive method to locate cable defect. However, locating a potential defect far from the cable head may be less accurate because of the signal amplitude attenuation and the interference parts. To solve the problem, this paper proposes an accuracy improvement method based on instantaneous filtering in time-frequency domain. The method extracts the frequency spectrum of the time-frequency signal, and then filters the spectrum and reconstructs the signal based on the difference between the signal and interference spectra, which can eliminate the interference and improve the location accuracy. In simulation, the location error of this method improves from 5.47 % to 0.57 %. In experiment, the proposed method reduces the location errors and magnifies the location peaks of the breakage defect, thermal aging defect, and ground faults. For the defects studied in this paper, the method improves the defect location accuracy and defect amplitude detectability of TFDR.

源语言英语
期刊论文编号114178
期刊Measurement: Journal of the International Measurement Confederation
226
DOI
出版状态已出版 - 28 2月 2024

学术指纹

探究 'An efficient accuracy improvement method for cable defect location based on instantaneous filtering in time-frequency domain' 的科研主题。它们共同构成独一无二的学术指纹。

引用此