跳到主要导航 跳到搜索 跳到主要内容

A numerical study on the effect of roof windbreak structures in an air-cooled system

  • Xi'an Jiaotong University

科研成果: 期刊稿件文章同行评审

20 引用 (Scopus)

摘要

The ambient wind velocity seriously affects the heat transfer performance in a Direct Air-Cooled Condenser (DACC). The heat transfer rate of an upstream heat exchanger unit is lower than that in other heat exchanger units under unfavorable ambient winds. The current work uses Computational Fluid Dynamics (CFD) to numerically simulate and analyze the effect of roof windbreak system on the DACC in a 2 × 350 MW power station. The distortion of the air flow, and the hot air recirculation rate at the fan inlet surface were studied at different ambient wind velocities. Our results show that the vertical length L1, inclined length L2, and inclination angle α on the roof windbreak line screen affect the performance of the DACC significantly. The analysis further shows that the optimal performance of the DACC can be achieved under the structure size of L1 = 30 m, α = 60°, and L2 = 5 m. The air flow decreases at the no wind or low wind velocity due to setting of the windbreak line screen. Therefore, the height of the platform needs to be adjusted to meet the suction space requirement for the fan.

源语言英语
页(从-至)684-693
页数10
期刊Applied Thermal Engineering
90
DOI
出版状态已出版 - 12 8月 2015

学术指纹

探究 'A numerical study on the effect of roof windbreak structures in an air-cooled system' 的科研主题。它们共同构成独一无二的指纹。

引用此