跳到主要导航 跳到搜索 跳到主要内容

A novel on-line monitoring method for three phase synchronization of medium voltage vacuum circuit breaker

  • Xi'an Jiaotong University

科研成果: 期刊稿件 › 文章 › 同行评审

21 引用 (Scopus)

摘要

Aiming at low reliability in short-time energy analysis method for on-line monitoring of circuit breaker mechanical state, the paper studies the method to eliminate interference noise by using trip coil current signal to improve the reliability of short-time energy analysis method. According to the analysis of vibration signal, this method can significantly improve the reliability of short-time energy analysis method to get the commencement instant of the vibration event from an adverse environment by rejecting most of the noise. The method is also compared with wavelet packets extraction algorithm. The method is tested on a ZN12-35 type vacuum circuit breaker and accurate switching synchronization status of the circuit breaker is obtained. The test results show that the new method obviously improve the accuracy of short-time energy analysis method to get the switching synchronization status of circuit breaker.

源语言英语
页(从-至)139-144
页数6
期刊Zhongguo Dianji Gongcheng Xuebao/Proceedings of the Chinese Society of Electrical Engineering
卷28
期12
出版状态已出版 - 25 4月 2008

学术指纹

探究 'A novel on-line monitoring method for three phase synchronization of medium voltage vacuum circuit breaker' 的科研主题。它们共同构成独一无二的学术指纹。

引用此