T1 - A Novel Directional Pilot Protection of Submarine Cables for Low Frequency Transmission System with Offshore Wind Power
AU - Gao, Xiaoping
AU - Song, Guobing
AU - Zhang, Chenhao
AU - Kang, Xiaoning
AU - Yan, Jifei
N1 - Publisher Copyright:
© 1986-2012 IEEE.
PY - 2025
Y1 - 2025
N2 - Low frequency transmission system (LFTS) has become a competitive method for long-distance offshore wind power transmission. However, traditional protections based on the fundamental frequency phasor may have poor performance since both ends of submarine cables connect with power electronic devices. First, the adaptability of traditional protections is analyzed. It is found that fault characteristics are weakened by typical control strategies. To enhance the characteristic difference between internal and external faults, an impedance construction method for grid-side converter (GSC) and modular multilevel matrix converter (M3C) is proposed. Then this paper proposes a directional pilot protection. For asymmetrical faults, the angle of negative-sequence impedance of GSC and M3C is determined by references of current loop controller. For symmetrical faults, adjusting coefficients of current loop reference in GSC helps the protection perform well under high-resistance faults. Building the sequence networks under different fault types, a phase selection method based on voltage magnitude is proposed. Finally, simulation tests are conducted in PSCAD/EMTDC, and the results demonstrate that the proposed impedance construction method can provide effective support for fault identification and the proposed protection performs well under various fault scenarios.
AB - Low frequency transmission system (LFTS) has become a competitive method for long-distance offshore wind power transmission. However, traditional protections based on the fundamental frequency phasor may have poor performance since both ends of submarine cables connect with power electronic devices. First, the adaptability of traditional protections is analyzed. It is found that fault characteristics are weakened by typical control strategies. To enhance the characteristic difference between internal and external faults, an impedance construction method for grid-side converter (GSC) and modular multilevel matrix converter (M3C) is proposed. Then this paper proposes a directional pilot protection. For asymmetrical faults, the angle of negative-sequence impedance of GSC and M3C is determined by references of current loop controller. For symmetrical faults, adjusting coefficients of current loop reference in GSC helps the protection perform well under high-resistance faults. Building the sequence networks under different fault types, a phase selection method based on voltage magnitude is proposed. Finally, simulation tests are conducted in PSCAD/EMTDC, and the results demonstrate that the proposed impedance construction method can provide effective support for fault identification and the proposed protection performs well under various fault scenarios.
KW - Directional pilot protection
KW - grid-side converter (GSC)
KW - impedance construction method
KW - low frequency transmission system (LFTS)
KW - modular multilevel matrix converter (M3C)