摘要
HVDC transmission systems have found wide applications in modern power systems and have produced a useful influence on the stability and security of power systems. The currently used protections for HVDC systems operate on the principles which have poor reliability and inadequate sensitivity. To overcome these problems, this paper presents a new whole-line quick-action protection principle for HVDC transmission lines. The proposed method, based on the boundary characteristics of the line, can distinguish internal faults from external ones using single-terminal current measurements only. The criterion of this protection has been formulated. Simulations on frequency-dependent parameter-line model and the field-recorded data of a ±500-kV HVDC system show that this method is valid and feasible. The proposed protection, sound and clear in principle and easy to implement, can be expected to become a primary protection of HVDC transmission.
| 源语言 | 英语 |
|---|---|
| 文章编号 | 6731591 |
| 页(从-至) | 599-607 |
| 页数 | 9 |
| 期刊 | IEEE Transactions on Power Delivery |
| 卷 | 30 |
| 期 | 2 |
| DOI | |
| 出版状态 | 已出版 - 1 4月 2015 |
学术指纹
探究 'A New Whole-Line Quick-Action Protection Principle for HVDC Transmission Lines Using One-End Current' 的科研主题。它们共同构成独一无二的指纹。引用此
- APA
- Author
- BIBTEX
- Harvard
- Standard
- RIS
- Vancouver