跳到主要导航 跳到搜索 跳到主要内容

A new indicator for a fair comparison on the energy performance of data centers

  • Jian Li
  • , Jakub Jurasz
  • , Hailong Li
  • , Wen Quan Tao
  • , Yuanyuan Duan
  • , Jinyue Yan
  • Mälardalen University
  • Tsinghua University
  • AGH University of Krakow
  • Hubei University of Arts and Science

科研成果: 期刊稿件文章同行评审

51 引用 (Scopus)

摘要

The power usage effectiveness (PUE) is commonly used as the key performance indicator to evaluate the energy performance of data centers. However, using only PUE cannot enable a fair comparison when data centers are operating in different regions, due to the unneglectable impacts of climatic conditions on the power consumption of cooling systems. To solve this problem, a new indicator, coefficient of PUE (COPUE), is proposed, which is defined as the ratio of the measured PUE of real data centers to the local benchmark PUE. The benchmark PUE is reckoned based on the current most commonly used cooling technology, which consists of water-cooled chillers and water cooling towers. A simplified method for calculating benchmark PUE is also developed. The degree hour of water cooling is introduced to consider the impacts of local climatic conditions. It presents the annual accumulated hours, in which chilled water is needed to satisfy the cooling demand of data centers. Through several case studies, COPUE has been proved to be an effective indicator for comparing the energy performance of data centers. When the same cooling technology is adopted, it can reflect how good the design and operation are; while, when different cooling technologies are adopted, it can be used to demonstrate which one is superior.

源语言英语
文章编号115497
期刊Applied Energy
276
DOI
出版状态已出版 - 15 10月 2020

联合国可持续发展目标

此成果有助于实现下列可持续发展目标:

  1. 可持续发展目标 7 - 经济适用的清洁能源
    可持续发展目标 7 经济适用的清洁能源

学术指纹

探究 'A new indicator for a fair comparison on the energy performance of data centers' 的科研主题。它们共同构成独一无二的指纹。

引用此