TY - JOUR
T1 - A ground fault section location method based on active detection approach for non-effectively grounded DC distribution networks
AU - Xu, Ruidong
AU - Song, Guobing
AU - Chang, Zhongxue
AU - Zhang, Chenhao
AU - Yang, Jiayi
AU - Yang, Xingang
N1 - Publisher Copyright:
© 2023 Elsevier Ltd
PY - 2023/10
Y1 - 2023/10
N2 - Identifying and locating the single-pole-to-ground fault for the non-effectively grounded DC distribution networks is highly challenging due to the topology arrangement limitations and the grounding mode. To solve this problem, a ground fault section location method based on active detection approach is proposed. Firstly, an approach based on an additional control strategy in coordination with a resonant branch setup is proposed to inject the detection signals. Then, the parameters of the resonant branch and the detection signals to be injected are obtained after careful consideration to ensure the optimal distribution characteristics of the injected signals. Finally, a protection principle based on a coordinating time interval scheme is proposed to locate and isolate the fault section according to the single terminal information. Simulation results show that the proposed method achieves excellent performance.
AB - Identifying and locating the single-pole-to-ground fault for the non-effectively grounded DC distribution networks is highly challenging due to the topology arrangement limitations and the grounding mode. To solve this problem, a ground fault section location method based on active detection approach is proposed. Firstly, an approach based on an additional control strategy in coordination with a resonant branch setup is proposed to inject the detection signals. Then, the parameters of the resonant branch and the detection signals to be injected are obtained after careful consideration to ensure the optimal distribution characteristics of the injected signals. Finally, a protection principle based on a coordinating time interval scheme is proposed to locate and isolate the fault section according to the single terminal information. Simulation results show that the proposed method achieves excellent performance.
KW - Active detection method
KW - DC distribution network
KW - Fault section location
KW - Non-effectively grounded system
KW - Single-pole-to-ground fault
UR - https://www.scopus.com/pages/publications/85159260969
U2 - 10.1016/j.ijepes.2023.109174
DO - 10.1016/j.ijepes.2023.109174
M3 - 文章
AN - SCOPUS:85159260969
SN - 0142-0615
VL - 152
JO - International Journal of Electrical Power and Energy Systems
JF - International Journal of Electrical Power and Energy Systems
M1 - 109174
ER -