跳到主要导航 跳到搜索 跳到主要内容

A fault-location method for VSC-HVDC transmission lines based on natural frequency of current

  • Xi'an Jiaotong University
  • Guangdong Power Grid Dispatch Control Center
  • Xi'an University of Science and Technology

科研成果: 期刊稿件文章同行评审

76 引用 (Scopus)

摘要

This paper presents a novel method for locating fault on VSC-HVDC transmission line using one terminal current data. The proposed method is developed based on the natural frequency of distributed parameter line model. In the presence of the large shunt capacitor at both terminals of the VSC-HVDC line, the high frequency traveling wave is approximately totally reflected at the terminals. It is found that the value of natural frequency of VSC-HVDC transmission line is only related to fault distance and wave speed. Using this characteristic, a single-end fault location method is developed. The natural frequency can be obtained by the PRONY algorithm. Compared with traveling wave method, this approach can use any section of the in-fault data to locate fault, without having to capture the instant at which wave-front arrives, which requires higher sampling rate. A short data window is sufficient for extracting natural frequency accurately in practice. The proposed method is verified using the frequency-dependent line model in EMTDC. The simulations have demonstrated validity, rapidity and accuracy of the proposed fault location algorithm.

源语言英语
页(从-至)347-352
页数6
期刊International Journal of Electrical Power and Energy Systems
63
DOI
出版状态已出版 - 12月 2014

学术指纹

探究 'A fault-location method for VSC-HVDC transmission lines based on natural frequency of current' 的科研主题。它们共同构成独一无二的学术指纹。

引用此