跳到主要导航 跳到搜索 跳到主要内容

A fault detection method based on active injection using dual active bridge converter in photovoltaic DC integration system

  • Jiayi Yang
  • , Guobing Song
  • , Ruidong Xu
  • , Zhongxue Chang
  • , Yiming Ren
  • Xi'an Jiaotong University

科研成果: 期刊稿件文章同行评审

4 引用 (Scopus)

摘要

Fault characteristics in photovoltaic DC integration systems exhibit short durations, making traditional protection principles less effective and unreliable. To address this challenge, a control-protection coordinated fault detection strategy based on active dual-frequency signal injection is proposed. By modifying the phase shift modulation of DAB converters, two specific frequency signals are injected with flexible control over frequency, amplitude, and duration according to system requirements. The fault characteristics under injected signals are subsequently analyzed, revealing that for healthy lines, the calculated capacitance closely matches the actual values, while for faulty lines, it consistently exceeds the true value. Based on this observation, a fault line identification method utilizing the Relative Capacitance Deviation (RCD) algorithm and fluctuation criteria is developed. Furthermore, a high-precision fault location method is introduced, employing parameter identification combined with a nonlinear interior-point optimization algorithm. The proposed method requires no communication or prior knowledge of line parameters, and demonstrates robust performance under transient resistance up to 200 Ω and noise levels up to 20 dB. Simulation results validate the effectiveness of the proposed method.

源语言英语
文章编号111926
期刊Electric Power Systems Research
248
DOI
出版状态已出版 - 11月 2025

联合国可持续发展目标

此成果有助于实现下列可持续发展目标:

  1. 可持续发展目标 7 - 经济适用的清洁能源
    可持续发展目标 7 经济适用的清洁能源

学术指纹

探究 'A fault detection method based on active injection using dual active bridge converter in photovoltaic DC integration system' 的科研主题。它们共同构成独一无二的指纹。

引用此