摘要
The high-altitude electromagnetic pulse has the characteristics of high field strength amplitude, wide distribution range and wide spectrum range. It can be coupled into the distribution transformer through the cables in wide-area. The induced currents with large change rates may pose threats to the turn-to-turn insulation or even phase-to-phase insulation of the transformer. In this case, electromagnetic pulse effect experiments are carried out on typical 10 kV oil immersed distribution transformer and dry-type distribution transformer in this paper, where their effect phenomena and threshold laws are compared and analyzed. An equivalent experimental platform for electromagnetic pulse effect experiment of 10 kV distribution transformer is built, which is mainly composed of 10 kV equivalent distribution system and electromagnetic pulse injection system. As a result, three phase nanosecond pulse currents can be injected into the 10 kV distribution transformer in common mode. Based on the experimental platform, the power-off state and power-on state tests are carried out and the effect data are obtained. The results show that both oil immersed transformer and dry-type transformer have the certain ability to resist electromagnetic pulses when the amplitude of the injected current is lower than around 500 A.
| 投稿的翻译标题 | Effect Experiments of 10 kV Distribution Transformer Excited by High-altitude Electromagnetic Pulse |
|---|---|
| 源语言 | 繁体中文 |
| 页(从-至) | 3119-3124 |
| 页数 | 6 |
| 期刊 | Gaodianya Jishu/High Voltage Engineering |
| 卷 | 49 |
| 期 | 7 |
| DOI | |
| 出版状态 | 已出版 - 31 7月 2023 |
关键词
- distribution transformer
- high-altitude electromagnetic pulse
- power-on state
- pulse injection
- real distribution system
- vulnerability
学术指纹
探究 '10 kV 配电变压器高空电磁脉冲效应实验研究' 的科研主题。它们共同构成独一无二的指纹。引用此
- APA
- Author
- BIBTEX
- Harvard
- Standard
- RIS
- Vancouver