辐射空调房间室内空气分布特性实验研究

  • Dalian University
  • Dalian University of Technology

科研成果: 期刊稿件文章同行评审

摘要

In this study, an electric-heating film was set up in a climate chamber to simulate the heat transfer in an external building envelope. Then, the indoor air distribution characteristics in a room with chilled ceiling and mixed ventilation were studied when the cooling loads were 83 or 111 W/ m2. The results show that a uniform vertical temperature profile below 1. 7 m as well as a non-uniform temperature profile above 1. 7 m existed when the ceiling surface temperatures varied from 15 to 23 ℃ and the supply air temperature was 22 ℃. The CO2 concentration was large in the occupied zone and small near the ceiling or floor. Moreover, the average vertical air temperature difference, turbulence intensity, and contaminant removal effectiveness were 0. 1-0. 2 ℃, 32%-38% and 0. 62-0. 86, respectively. Therefore, the changes in the ceiling surface temperature slightly affected the vertical air-temperature difference and turbulence intensity, whereas they clearly influenced the contaminant removal effectiveness.

投稿的翻译标题Indoor Air Distribution Characteristics in a Room with Chilled Ceiling and Mixed Ventilation
源语言繁体中文
页(从-至)144-152
页数9
期刊Journal of Refrigeration
40
4
DOI
出版状态已出版 - 8月 2019

关键词

  • chilled ceiling
  • contaminant removal effectiveness
  • mixed ventilation
  • turbulence intensity
  • vertical air temperature difference