西北电网 330 kV 尖樊线人工短路试验中接地距离保护适应性分析

  • Huaiqiang Li
  • , Jiankang Zhang
  • , Jiaheng Jiang
  • , Longfei Ren
  • , Chenhao Zhang
  • , Guobing Song
  • State Grid Corporation of China
  • Xi'an Jiaotong University

科研成果: 期刊稿件文章同行评审

7 引用 (Scopus)

摘要

The fault characteristics of renewable energy plants represented by wind power have a new impact on the additional impedance of traditional distance protection,leading to the reduction of protection performance. However,the existing research on the adaptability of distance protection lacks the analysis of the single-phase grounding cases. Therefore,based on the data of two artificial short circuit tests conducted by Northwest Branch of State Grid at Jian-Fan transmission line and the fault characteristics of wind farms under various control strategies,the additional impedance coefficient of grounding distance protection under single-phase grounding is analyzed,and then the protection adaptability is judged. It is found that the additional impedance coefficient of the grid side protection is small,and the fault current of power supply on both sides has little influence on the protection. However,the additional impedance coefficient of the wind farm side protection is large,and the fault current of the power supply on both sides has a great influence on the protection,leading to protection rejection.

投稿的翻译标题Adaptability analysis of grounding distance protection of 330 kV Jian-Fan transmission line artificial short circuit test in Northwest Branch of State Grid
源语言繁体中文
页(从-至)67-74 and 90
期刊Dianli Zidonghua Shebei/Electric Power Automation Equipment
44
3
DOI
出版状态已出版 - 3月 2024

联合国可持续发展目标

此成果有助于实现下列可持续发展目标:

  1. 可持续发展目标 7 - 经济适用的清洁能源
    可持续发展目标 7 经济适用的清洁能源

关键词

  • additional impedance coefficient
  • artificial short circuit test
  • fault characteristics
  • grounding distance protection
  • outgoing line of renewable energy plant
  • wind farms