跳到主要导航 跳到搜索 跳到主要内容

混合式高压直流断路器分断过程电磁瞬态建模和测试

  • Longlong Chen
  • , Xiaoguang Wei
  • , Chongqing Jiao
  • , Guangfu Tang
  • , Xiang Cui
  • , Chong Gao
  • North China Electric Power University
  • Global Energy Interconnection Research Institute Co. Ltd., Beijing

科研成果: 期刊稿件文章同行评审

16 引用 (Scopus)

摘要

HVDC circuit breaker is the core equipment of the DC grid. It is required to cut off large currents of tens to thousands of amperes within a few milliseconds. The strong electromagnetic disturbance during the breaking process may cause interference, which will in return influence IGBTs and the proper work of the secondary equipment. Due to the lack of standards for electromagnetic driver tests, the theoretical analysis and testing are combined to analyze the electromagnetic transient process. After that, a test is firstly carried out in the laboratory to verify the actual collector emitter (VCE) and gate drive (VGE) in a 500kV hybrid DC circuit breaker with a maximum breaking current of 25kA, and the tests signals were further analyzed in both time and frequency domains to extract accurate interference characteristics. The results indicate that the interference characteristics of VCE/VGE during the breaking process is similar to the surge test and damped oscillation wave, while the power interference characteristics are closer to the damped oscillation waves. Therefore, these two kinds of anti-electromagnetic interference capabilities should be considered in design and test.

投稿的翻译标题Electromagnetic Transient Modeling and Test of Hybrid DC Circuit Breaker
源语言繁体中文
页(从-至)5261-5271
页数11
期刊Diangong Jishu Xuebao/Transactions of China Electrotechnical Society
36
24
DOI
出版状态已出版 - 25 12月 2021

关键词

  • 500kV DC breaker
  • Current breaking
  • Electromagnetic interference
  • Interference test

学术指纹

探究 '混合式高压直流断路器分断过程电磁瞬态建模和测试' 的科研主题。它们共同构成独一无二的学术指纹。

引用此