摘要
The blind recloser of automatic reclosing in a permanent fault brings secondary impact to the distribution network. Thus an active detection scheme for identifying the permanent fault using a phase segregated switch is proposed. In the case of a transient ground fault, the transmission line is equivalent to a capacitance model, and the transient voltage and current are used to obtain the calculated capacitance by the least squares method. The calculated capacitance is similar to the actual value and effectively does not change with time. In the case of a permanent ground fault, the transmission line does not conform to the capacitance model, and the calculated capacitance may be negative and changes drastically with time. In the case of a phase-to-phase fault, one faulty phase is closed, and the existence of the fault point will cause a difference in the transient response of the unclosed phases and there is a large transient line voltage between unclosed phases. For the ground fault, a permanent fault identification criterion is constructed to identify the capacitance parameter using the idea of model identification. For the phase-to-phase fault, a permanent fault identification criterion using transient line voltage is constructed. The PSCAD simulation results show that the proposed method can accurately identify the permanent fault of a distribution network at different fault locations with different transition resistances.
| 投稿的翻译标题 | Permanent fault identification method of a distribution network based on detection using a phase segregated switch |
|---|---|
| 源语言 | 繁体中文 |
| 页(从-至) | 11-21 |
| 页数 | 11 |
| 期刊 | Dianli Xitong Baohu yu Kongzhi/Power System Protection and Control |
| 卷 | 51 |
| 期 | 5 |
| DOI | |
| 出版状态 | 已出版 - 1 3月 2023 |
关键词
- detection
- distribution network
- permanent fault identification
- phase segregated switch
- transient process
学术指纹
探究 '利用分相开关探测的配电网永久性故障识别方法' 的科研主题。它们共同构成独一无二的学术指纹。引用此
- APA
- Author
- BIBTEX
- Harvard
- Standard
- RIS
- Vancouver