跳到主要导航 跳到搜索 跳到主要内容

减小电压暂降深度及持续时间的单相重合闸时序方案

  • Zhenfeng Liang
  • , Qing Zhang
  • , Guobing Song
  • , Zhanfeng Fan
  • , Baowei Li
  • Xi'an University of Technology
  • XJ Group Corporation

科研成果: 期刊稿件 › 文章 › 同行评审

6 引用 (Scopus)

摘要

In order to reduce the voltage sag depth and duration of sensitive load when the single-phase circuit breaker reclosing fails, a scheme of single-phase reclosing sequence is proposed. When a single-phase grounding fault occurs on the line, the protections on both sides act and fault phase breakers are tripped. The concept of fault component is used to construct the fault additional state network. Additional source is added to each end of the line to calculate the fault component voltage of the sensitive load node. The reclosing sequence is determined according to the magnitude of fault component voltage of sensitive load node. The side with smaller magnitude is determined to reclose first. After one side of the line is reclosed, the magnitude of line voltage is used to judge whether the reclosing is open or not at the other side. PSCAD/EMTDC simulation results show that this method is not affected by transition resistance and fault location and can improve the voltage power quality of sensitive load.

投稿的翻译标题Single-phase Reclosing Sequence for Reducing Voltage Sag Depth and Duration
源语言繁体中文
页(从-至)165-170
页数6
期刊Dianli Xitong Zidonghua/Automation of Electric Power Systems
卷43
期9
DOI
出版状态已出版 - 10 5月 2019

关键词

  • Fault component
  • Reclosing sequence
  • Sensitive load
  • Single-phase reclosing
  • Voltage sag

学术指纹

探究 '减小电压暂降深度及持续时间的单相重合闸时序方案' 的科研主题。它们共同构成独一无二的学术指纹。

引用此