跳到主要导航 跳到搜索 跳到主要内容

一 种 适 用 于 混 合 三 端 直 流 系 统 的 纵 联 保 护 方 案

  • Xi'an University of Science and Technology

科研成果: 期刊稿件 › 文章 › 同行评审

4 引用 (Scopus)

摘要

To improve the transmission reliability of multi-terminal systems,this paper proposes a hybrid three-terminal DC trans-mission line pilot protection method based on the Mann-Kendall test method. The method uses the T-connected bus three terminal current fault component to determine the fault area,then uses the Mann-Kendall test method to analyze the changing trend of the current at both ends of the line in the fault area,and realizes the fault type identification and the fault pole selection. Finally,the model is built in PSCAD/EMTDC and different fault conditions are simulated,and the proposed protection method is verified with MATLAB. Simulation results show that the proposed method can operate reliably within 2.5 ms under various fault conditions,with good quick-action,and has strong resistance to noise interference and transition resistance.

投稿的翻译标题A Pilot Protection Scheme for Hybrid Three-terminal DC Systems
源语言繁体中文
页(从-至)125-135
页数11
期刊Hunan Daxue Xuebao/Journal of Hunan University Natural Sciences
卷50
期4
DOI
出版状态已出版 - 4月 2023

关键词

  • Mann-Kendall test method
  • electric fault currents
  • hybrid three-terminal DC transmission lines
  • phase-mode transforma⁃ tion
  • relay protection

学术指纹

探究 '一 种 适 用 于 混 合 三 端 直 流 系 统 的 纵 联 保 护 方 案' 的科研主题。它们共同构成独一无二的学术指纹。

引用此