Abstract
The paper mainly described the upgrade study of UHVDC converter valve type test capability, which will meet all the test requirements of ± 800kV/6250A and ±1100kV/5454A thyristor valves. By optimizing and upgrading rectifier transformer and water-cooled systems, especially that a new synthetic fault test circuit, the operational test capability reaches rated current 7500 A, and fault current peak is 62 kA. In addition, surface electric field intensity on shielding cases of the impulse test equipment is calculated by using Galerkin boundary element method. According to existing conditions, a feasible measure is proposed, which can be employed to decrease electric field dramatically and avoid corona discharge of shielding cases. Another effort in the dielectric test is theoretically analysis and test study for the DC test equipment with rated voltage ±2400kV. Finally, the parameters and results for the ± 800kV/6250A and ±1100kV/5454A prototype will be presented.
| Original language | English |
|---|---|
| Title of host publication | POWERCON 2014 - 2014 International Conference on Power System Technology |
| Subtitle of host publication | Towards Green, Efficient and Smart Power System, Proceedings |
| Publisher | Institute of Electrical and Electronics Engineers Inc. |
| Pages | 2345-2352 |
| Number of pages | 8 |
| ISBN (Electronic) | 9781479950324 |
| DOIs | |
| State | Published - 18 Dec 2014 |
| Event | 2014 International Conference on Power System Technology, POWERCON 2014 - Chengdu, China Duration: 20 Oct 2014 → 22 Oct 2014 |
Publication series
| Name | POWERCON 2014 - 2014 International Conference on Power System Technology: Towards Green, Efficient and Smart Power System, Proceedings |
|---|
Conference
| Conference | 2014 International Conference on Power System Technology, POWERCON 2014 |
|---|---|
| Country/Territory | China |
| City | Chengdu |
| Period | 20/10/14 → 22/10/14 |
UN SDGs
This output contributes to the following UN Sustainable Development Goals (SDGs)
-
SDG 7 Affordable and Clean Energy
Keywords
- Dielectric test
- Operational test
- Thyristor valve
- Type test