Abstract
A time domain fault location algorithm for parallel transmission lines is proposed in this paper. Based on RL model, the novel fault location method is implemented by calculating voltage distribution using one terminal voltage and current, and expressing fault current using differential component current, and then the fault can be located by the relationship of voltage and current in fault point. For the fault location is carried out in time domain, which has some merits of short data window and low computation capacity. Results simulated by using distributed parameter model show that the proposed algorithm is practicable for constructing distance protection. And a technique is given to improve the accuracy of the method.
| Original language | English |
|---|---|
| Pages (from-to) | 34-38+42 |
| Journal | Dianli Xitong Baohu yu Kongzhi/Power System Protection and Control |
| Volume | 37 |
| Issue number | 20 |
| State | Published - 16 Oct 2009 |
Keywords
- Fault location
- One terminal
- Parallel transmission lines
- RL model
- Time domain
Fingerprint