Skip to main navigation Skip to search Skip to main content

Thermal performance of split-flow heat exchangers

  • B. Spang
  • , Y. Xuan
  • , W. Roetzel
  • Helmut-Schmidt-University

Research output: Contribution to journalArticlepeer-review

1 Scopus citations

Abstract

Thermal analysis is carried out for split-flow heat exchangers with an even number of tube passes, arbitrary entrance and exit locations of the shellside flow, arbitrary division of the shellside fluid and variable NTU. A closed form solution is presented for calculating the temperature at a given position and the thermal effectiveness. The thermal performance of the split-flow exchanger is compared with that of the conventional shell and tube exchanger. The shellside pressure drop and the optimum entrance and exit locations of the shellside flow in the split-flow exchanger are discussed.

Original languageEnglish
Pages (from-to)863-874
Number of pages12
JournalInternational Journal of Heat and Mass Transfer
Volume34
Issue number3
DOIs
StatePublished - Mar 1991

Fingerprint

Dive into the research topics of 'Thermal performance of split-flow heat exchangers'. Together they form a unique fingerprint.

Cite this