Abstract
In on-line monitoring tanδ of power equipment, the harmonic analysis based on conventional FFT brings significant errors because of the truncation of power frequency signal and unsynchronized sampling sequence. In this paper, the window and interpolation algorithm is derived, and a practical interpolation formula with Blackman-Harris window is proposed. For the unsynchronized sampling sequence caused by frequency fluctuation of power system, the simulation is performed via MATLAB code on the conventional FFT algorithm the interpolation algorithm with Blackman window, and the interpolation algorithm with Blackman-Harris window, respectively. The simulation results show that the interpolation algorithm with Blackman-Harris window can effectively reduce the measurement error and increase the precision, which satisfies the requirement for on-line monitoring tanδ of power equipment.
| Original language | English |
|---|---|
| Pages (from-to) | 57-61 |
| Number of pages | 5 |
| Journal | Gaoya Dianqi/High Voltage Apparatus |
| Volume | 45 |
| Issue number | 2 |
| State | Published - 2009 |
Keywords
- FFT
- Frequency fluctuation
- Harmonic analysis
- On-line tanδ Monitoring
- Unsynchronized sampling sequence
- Window and interpolation algorithm
Fingerprint
Dive into the research topics of 'Theoretical and simulation study on high accuracy FFT algorithm for tanδ monitoring'. Together they form a unique fingerprint.Cite this