Skip to main navigation Skip to search Skip to main content

Studying the performance of a liquid desiccant indirect evaporative cooling system

  • Xi'an Jiaotong University
  • China Northwest Architecture Design and Research Institute Co. Ltd.

Research output: Contribution to journalConference articlepeer-review

12 Scopus citations

Abstract

A liquid desiccant-indirect evaporative cooling (LD-IEC) system has been proposed. The design is able to dehumidify and cool the product air simultaneously in one unit. A computational model has been developed to determine the performance of the heat and mass transfer process. The validation of the model demonstrated good agreement with the experimental data to within 10%. The detailed air treatment process has been theoretically studied. The thermal performance of the LD-IEC has been evaluated. Simulation results showed that the outlet temperature and humidity ratio were influenced by the liquid desiccant film length, intake air temperature, and intake air humidity ratio. For a specific inlet temperature and humidity ratio condition, a desired outlet condition can be obtained by adjusting the length of the liquid desiccant film.

Original languageEnglish
Pages (from-to)5659-5665
Number of pages7
JournalEnergy Procedia
Volume158
DOIs
StatePublished - 2019
Event10th International Conference on Applied Energy, ICAE 2018 - Hong Kong, China
Duration: 22 Aug 201825 Aug 2018

Keywords

  • Air-conditioning
  • Dehumidification
  • Heat and mass transfer
  • Indirect evaporative cooling
  • Mathematical model

Fingerprint

Dive into the research topics of 'Studying the performance of a liquid desiccant indirect evaporative cooling system'. Together they form a unique fingerprint.

Cite this