Skip to main navigation Skip to search Skip to main content

Study on two-phase flow instabilities in internally-ribbed tubes by using frequency domain method

  • Xi'an Jiaotong University

Research output: Contribution to journal › Article › peer-review

27 Scopus citations

Abstract

A new mathematical model was proposed in this paper based on the frequency domain theory to investigate two-phase flow instabilities in internally-ribbed tubes. Two significant improvements were made to conventional models, one of which was that the heat storage of the tube wall metal, the internal wall heat flux and the external wall heat flux were considered as dynamic parameters, and another one was that a new feedback relationship was established. The new model was verified by comparing the prediction results to both the corresponding experimental data in literature and the results obtained with SIMULINK. Then the two-phase flow instabilities in internally-ribbed tubes were studied systematically. It was shown that the stability of two-phase flows increased with pressure, mass flux or inlet resistance coefficient. It was also found that there existed a worst point of the stability (WPS) of the two-phase flows when the inlet fluid subcooling increased. Two-phase flows in the 6-head ribs internally-ribbed tube (38.1 × 7.5 mm) was more stable than that in the 4-head ribs internally-ribbed tube (28 × 5.41 mm). The present model and results could provide guidance for the design and operation of boilers.

Original languageEnglish
Pages (from-to)1-13
Number of pages13
JournalApplied Thermal Engineering
Volume65
Issue number1-2
DOIs
StatePublished - Apr 2014

Keywords

  • Critical heat flux
  • Frequency domain theory
  • Internally-ribbed tube
  • SIMULINK
  • Two-phase flow instability

Fingerprint

Dive into the research topics of 'Study on two-phase flow instabilities in internally-ribbed tubes by using frequency domain method'. Together they form a unique fingerprint.

Cite this