Abstract
To get rid of the latent danger induced by the current neutral point grounding way of transforms in Xi'an power grid, an optimal grounding method of 330 kV auto-transformers and 110 kV transforms through a low reactance is proposed. The simulation results reveal that after grounding through low reactance with appropriate value, the single-phase grounding short-circuit current on the 110 kV bus-bar of 330 kV auto-transform decreases clearly, and the over-voltage on neutral point of other 110 kV transforms is significantly reduced to a lower level, which guarantee safe insulation of neutral point and enhance reliability of the power grid.
| Original language | English |
|---|---|
| Pages (from-to) | 91-94 |
| Number of pages | 4 |
| Journal | Gaoya Dianqi/High Voltage Apparatus |
| Volume | 46 |
| Issue number | 2 |
| State | Published - 2010 |
Keywords
- Low reactance
- Neutral point
- Over-voltage
- Short-circuit current