Study on Multi-Parameter Detection Methods of Buffer Layer Ablation for 110kV Cable

Research output: Chapter in Book/Report/Conference proceedingConference contributionpeer-review

Abstract

In recent years, the breakdown accidents of high voltage cable caused by the ablation of buffer layer in high voltage cable occurs frequently, which has seriously affected the safety and stability of power grid. In this paper, by studying the development process of ablation of buffer layer for 110kV cable, the ultrasonic, electrical and thermal characteristic signals generated by ablation defects are studied, and the evolution process of characteristic parameters of ablation defects is obtained. According to the detection results, the buffer layer ablation is divided into initial stage with only temperature change and rapid development stage with the generation of significant ultrasonic and electrical signals as well as a rapid increase of temperature.

Original languageEnglish
Title of host publication2023 2nd Asia Power and Electrical Technology Conference, APET 2023
PublisherInstitute of Electrical and Electronics Engineers Inc.
Pages171-175
Number of pages5
ISBN (Electronic)9798350359428
DOIs
StatePublished - 2023
Event2nd Asia Power and Electrical Technology Conference, APET 2023 - Shanghai, China
Duration: 28 Dec 202330 Dec 2023

Publication series

Name2023 2nd Asia Power and Electrical Technology Conference, APET 2023

Conference

Conference2nd Asia Power and Electrical Technology Conference, APET 2023
Country/TerritoryChina
CityShanghai
Period28/12/2330/12/23

Keywords

  • buffer layer ablation
  • development process
  • electrical signals
  • thermal signals
  • ultrasonic signals