Abstract
The Z-source inverter topology and operating principle were analyzed, the main work states were derived and the control strategy was studied. According to control requirement of grid-connected PV power generation system, and requirement of electricity quality, a fuzzy PI controller for capacitor voltage of Z-source inverter was presented to overcome bad transient performance of traditional PI controller. The simulation and experimental results verified the rationality and validity of proposed control strategy.
| Original language | English |
|---|---|
| Pages (from-to) | 971-978 |
| Number of pages | 8 |
| Journal | Taiyangneng Xuebao/Acta Energiae Solaris Sinica |
| Volume | 35 |
| Issue number | 6 |
| State | Published - Jun 2014 |
Keywords
- Fuzzy PI controller
- Grid-connected
- PV power generation
- Shoot-through
- Z-source inverter