Skip to main navigation Skip to search Skip to main content

Study of the Arc Interruption Performance of SF6 Alternative Gases in Load Switch

  • Xi'an Jiaotong University
  • Shenzhen Power Supply Corporation

Research output: Chapter in Book/Report/Conference proceedingConference contributionpeer-review

9 Scopus citations

Abstract

SF 6gas is widely used in power equipment for its excellent arc extinguishing and insulation properties. However, SF 6is a strong greenhouse effect gas with a global warming potential (GWP) of 23, 500 times that of CO. Therefore, the Kyoto Protocol signed in 1997 has included SF 6in one of the six greenhouse gases which are restricted for use. Nowadays, finding an environmentally friendly alternative gas for SF 6is a hot issue in the world. The research on SF 6environmental alternative gas has made great progress these years. C5F10O is considered the most likely gas to replace SF6in the near future. Although CF10Ohas a good arc extinguishing property in general, the arc extinguishing mechanism of it in the load switch is not clear. Because arc extinguishing is a complex physical and chemical process involving the interaction of gas flow fields, electromagnetic fields, and ablation the nozzle materials. In this paper, by combining the computational fluid dynamics (CFD) analysis and the Mayr arc model the interruption processes for a load switch filled with 5%C4F7N/COand 5%CF10O/COat 0.135 MPa, as well as pure SF6 and COat 0.135 MPa, are investigated. The time constant ? and arc cooling coefficient Q at the current zero point is calculated based on the Mayr equation. In the end, the critical values of the rising rate of the recovery voltage (RRRV) are obtained. These parameters are the most important issues to determine whether breaking success or not. Through the analysis of the post arc medium recovery, the arc extinguishing performance of different gas medium can be theoretically and quantitatively evaluated. It can provide a sufficient theoretical basis to enhance the arc extinguishing ability of the load switch through the CFD analysis.

Original languageEnglish
Title of host publication7th IEEE International Conference on High Voltage Engineering and Application, ICHVE 2020 - Proceedings
PublisherInstitute of Electrical and Electronics Engineers Inc.
ISBN (Electronic)9781728155111
DOIs
StatePublished - 6 Sep 2020
Event7th IEEE International Conference on High Voltage Engineering and Application, ICHVE 2020 - Beijing, China
Duration: 6 Sep 202010 Sep 2020

Publication series

Name7th IEEE International Conference on High Voltage Engineering and Application, ICHVE 2020 - Proceedings

Conference

Conference7th IEEE International Conference on High Voltage Engineering and Application, ICHVE 2020
Country/TerritoryChina
CityBeijing
Period6/09/2010/09/20

Keywords

  • Arc extinguishing
  • C5F10O
  • Load switch
  • MHD simulation
  • SF6 alternative gases