Single phase line-broken fault detection and location based on differential voltage in radial distribution network

  • Zhongxue Chang
  • , Zhihao Zeng
  • , Minna Dou
  • , Zhihua Zhang
  • , Guobing Song

Research output: Contribution to journalArticlepeer-review

3 Scopus citations

Abstract

Single phase line-broken (SPLB) fault is one kind of high impedance fault (HIF). When a SPLB fault occurs, there are four scenarios: SPLB fault with neither side conductors grounded (SPLB-NSCG), with source side conductor grounded only (SPLB-SSCG), with load side conductor grounded only (SPLB-LSCG), with both side conductors grounded (SPLB-BSCG). Traditional HIF detection methods using current or voltage characteristics have low sensitivity to SPLB fault. In this paper, voltage characteristics are analysed firstly in the cases of the first three scenarios of SPLB fault, respectively. Theoretical analysis finds that the voltage at both the sides of the disconnection point is significantly different. A high sensitive SPLB fault detection method based on differential voltage is proposed for radial distribution network with different data synchronization ability. Finally, SPLB fault location methods based on centralized intelligent mode feeder automation (FA) and intelligent distributed mode FA are proposed. Simulations based on PSCAD verify that the proposed SPLB fault detection method is feasible, highly sensitive and immune to the neutral grounded mode, fault scenarios and fault resistance.

Original languageEnglish
Pages (from-to)116-127
Number of pages12
JournalIET Generation, Transmission and Distribution
Volume17
Issue number1
DOIs
StatePublished - Jan 2023

Keywords

  • distribution networks
  • fault location
  • overvoltage
  • power distribution faults

Fingerprint

Dive into the research topics of 'Single phase line-broken fault detection and location based on differential voltage in radial distribution network'. Together they form a unique fingerprint.

Cite this