Abstract

It is important to study adaptive reclosure which can improve the success rate of reclsosure and avoid reclosing to the fault lines because of defects of conventional auto-reclosure. This paper discusses the conception of transient fault and permanent fault, and distinguishes them based on whether the fault point current is zero. It is pointed out that the success of auto-reclosure is not only decided by fault character, but also is influenced by reclosing time sequence. So the adaptive reclosure should contain both distinguishing permanent faults from transient faults and optimization of reclosing time sequence. The single-phase adaptive reclosure, the three-phase reclosure and the adaptive reclosure for double circuits are respectively reviewed. The prospects in adaptive reclosure are described.

Original languageEnglish
Pages (from-to)140-147
Number of pages8
JournalDianli Xitong Baohu yu Kongzhi/Power System Protection and Control
Volume41
Issue number6
StatePublished - 16 Mar 2013

Keywords

  • Adaptive reclosure
  • Permanent faults
  • Power system
  • Protection relaying
  • Single-phase reclosure
  • Three-phase reclosure
  • Transient faults
  • Transmission lines

Fingerprint

Dive into the research topics of 'Research review of adaptive reclosure in transmission lines'. Together they form a unique fingerprint.

Cite this