Skip to main navigation Skip to search Skip to main content

PLL Based Sub-/Super-Synchronous Resonance Damping Controller for D-PMSG Wind Farm Integrated Power Systems

  • Songhao Yang
  • , Ruixin Shen
  • , Jin Shu
  • , Tao Zhang
  • , Yujun Li
  • , Baohui Zhang
  • , Zhiguo Hao
  • Xi'an Jiaotong University
  • Thermal Power Research Institute

Research output: Contribution to journalArticlepeer-review

48 Scopus citations

Abstract

Existing sub-/super-synchronous (SSO) suppression methods for the direct-drive permanent magnet synchronous generators (D-PMSG) integrated power systems are mainly achieved by external devices or sub-synchronous resonance damping controller (SSRDC) at the converters, facing challenges of considerable control costs, complex parameters tuning, or inadaptability to various operating conditions. To address these problems, this paper proposes an adaptive SSRDC based on the phase-locked loop (PLL) for D-PMSG integrated power systems. Firstly, the PLL parameter is found critical to SSO suppression by a comprehensive sensitivity analysis on the dominant poles of the impedance closed-loop transfer function. Motivated by this finding, this paper then designs a PLL-based SSRDC, which features a simple structure, easy parameter tuning, and flexible adaptability to various operating modes. The simplicity in structure is guaranteed by the avoidance of phase compensation. Benefiting from the simple structure, only one key parameter needs to be tuned. Moreover, two principles of parameter tuning are proposed to enhance the efficiency, robustness, and adaptability of the proposed SSRDC. The controller-hardware-in-the-loop (CHIL) tests verify the validity of the proposed SSRDC under various operating conditions. Finally, some concerns about this method such as frequency estimation, computational efficiency and potential impacts on PLL are thoroughly analyzed and clarified.

Original languageEnglish
Pages (from-to)2370-2384
Number of pages15
JournalIEEE Transactions on Energy Conversion
Volume37
Issue number4
DOIs
StatePublished - 1 Dec 2022

Keywords

  • SSO suppression
  • Sub-/Super-synchronous Oscillation (SSO)
  • Super-synchronous Resonance Damping Controller (SSRDC)
  • direct-drive permanent magnet synchronous generators (D-PMSG)
  • phase-locked loop (PLL)
  • the controller-hardware-in-the-loop (CHIL) test

Fingerprint

Dive into the research topics of 'PLL Based Sub-/Super-Synchronous Resonance Damping Controller for D-PMSG Wind Farm Integrated Power Systems'. Together they form a unique fingerprint.

Cite this