Skip to main navigation Skip to search Skip to main content

Phase Current Based Fault Section Location for Single-Phase Grounding Fault in Non-Effectively Grounded Distribution Network

  • Zhongxue Chang
  • , Qingyu He
  • , Nana Chang
  • , Weibin Tan
  • , Wei Zhang
  • , Zhihua Zhang
  • , Guobing Song
  • Xi'an Jiaotong University
  • Zhuhai XJ Electric Company Ltd
  • State Grid Shaanxi Electric Power Research Institute

Research output: Contribution to journal › Article › peer-review

17 Scopus citations

Abstract

A novel single-phase grounding (SPG) fault detection and location methods in non-effectively grounded distribution network based on fault component of phase current is proposed in this paper. First, the fault component networks are built and transient characteristics of the fault components of phase current under SPG fault are analyzed based on the Karrenbauer Transformation. Then the SPG fault detection method based on the correlation coefficient of fault component of phase current measured by adjacent intelligent electronic devices (IEDs) is proposed and the section location methods based on intelligent distributed feeder automation mode and centralized feeder automation mode is proposed respectively. Finally, the proposed method is validated by simulation based on PSCAD and fault recording data. Results show that the proposed methods are feasible. Compared to zero-sequence voltage and current based SPG fault detection methods, the proposed method does not need zero-sequence current transformer and potential transformer. Besides, the proposed method can select the faulty phase automatically without using voltage signals.

Original languageEnglish
Pages (from-to)5242-5250
Number of pages9
JournalIEEE Transactions on Industry Applications
Volume61
Issue number3
DOIs
StatePublished - 2025

Keywords

  • Correlation coefficient
  • Non-effectively grounded distribution network
  • fault component
  • fault section location
  • feeder automation
  • phase current
  • single-phase grounding (SPG) fault

Fingerprint

Dive into the research topics of 'Phase Current Based Fault Section Location for Single-Phase Grounding Fault in Non-Effectively Grounded Distribution Network'. Together they form a unique fingerprint.