Permanent fault identification method based on parameter identification for photovoltaic access to distribution network

Research output: Contribution to journalArticlepeer-review

17 Scopus citations

Abstract

In order to solve the problem of pre-acceleration auto reclosing is coincident with the permanent fault when the photovoltaic system is connected to the distribution network, a new method is proposed for permanent fault diagnosis of three phase auto reclosing for photovoltaic power distribution network. This method takes the transient fault model as reference, the mathematical model of linear model of line fault is established, the least square algorithm is used to identify the line phase capacitance, a permanent fault identification criterion is established based on the identification error of the phase to phase capacitance. The recognition value is close to the actual value when the line is transient fault; the difference between the recognition value and the real value is larger and when the line is permanent fault. A simulation model is established by using the PSCAD, the transient fault and permanent fault are simulated for the grid connected photovoltaic system. Simulation results show that the proposed method can identify the fault types of the grid connected PV system, and the correctness and validity of the method is verified.

Original languageEnglish
Pages (from-to)1-7
Number of pages7
JournalDianli Xitong Baohu yu Kongzhi/Power System Protection and Control
Volume45
Issue number16
DOIs
StatePublished - 16 Aug 2017

Keywords

  • Capacitance parameter
  • Distribution network
  • Fault discrimination
  • Parameter identification
  • Photovoltaic system

Fingerprint

Dive into the research topics of 'Permanent fault identification method based on parameter identification for photovoltaic access to distribution network'. Together they form a unique fingerprint.

Cite this