Abstract

This paper presents a control scheme which allows wireless-paralleled inverters to share linear or nonlinear load. It can be used in large scale uninterruptible power supply (UPS) systems and distributed power systems. This control scheme is based on digital signal processor (DSP) to measure output power of high performance inverter modules, and it based on frequency-droop and amplitude-droop scheme to control the output voltage. The high performance inverter modules have inner filter capacitor current loops; and the output voltage can maintain high-quality sine-wave. An experiment system was built to verify this control scheme, and the results indicate the inverters in parallel connection realize load current sharing.

Original languageEnglish
Pages (from-to)94-98
Number of pages5
JournalZhongguo Dianji Gongcheng Xuebao/Proceedings of the Chinese Society of Electrical Engineering
Volume23
Issue number12
StatePublished - Dec 2003

Keywords

  • Load sharing
  • SPWM inverter
  • Wireless parallel operation

Fingerprint

Dive into the research topics of 'Parallel operation of sinusoid wave inverters without control interconnections'. Together they form a unique fingerprint.