Operation and control of static var generator for voltage unbalance mitigation

Research output: Contribution to journalArticlepeer-review

8 Scopus citations

Abstract

Voltage unbalance has a great impact on power electronics equipment. This paper provided a detailed analysis of SVG performance under unbalanced voltage with traditional control method. Furthermore, a novel control strategy was proposed to mitigate voltage unbalance and at the same time extend the functions of SVG. Besides compensating reactive power, SVG can also mitigate unbalanced voltage at the point of common coupling (PCC) when severe negative sequence voltage exists. The SVG operates as a voltage source controlled by the negative sequence voltage at the PCC. The relationships between all the parameters and the compensating characteristics were analyzed in detail. Simulation and experiment results verify the satisfactory performance of the SVG in mitigating voltage unbalance with the proposed control strategy.

Original languageEnglish
Pages (from-to)69-74
Number of pages6
JournalDiangong Jishu Xuebao/Transactions of China Electrotechnical Society
Volume21
Issue number8
StatePublished - Aug 2006

Keywords

  • Fundamental negative sequence voltage
  • SVG
  • Voltage controlled voltage source
  • Voltage unbalance

Fingerprint

Dive into the research topics of 'Operation and control of static var generator for voltage unbalance mitigation'. Together they form a unique fingerprint.

Cite this