Numerical study on indoor air quality of commercial kitchen in china

Research output: Chapter in Book/Report/Conference proceedingConference contributionpeer-review

1 Scopus citations

Abstract

Indoor air quality of commercial kitchen is investigated and analyzed through velocity, temperature, humidity, and CO2 concentration under different air change rate and supply air temperature. the best air change rate is 30 times per hour and air supply temperature is 301.15K for kitchen, the mean value of the minimum velocity and standard deviation is 0.410m/s and 0.129 respectively, the maximum of the average concentration of CO2 is 659.78ppm, which is less than the acceptance criteria (CO2< 1000ppm), and the energy utilization coefficient is maximum of 1.352. Research results show that this air supply mode can optimize indoor air quality.

Original languageEnglish
Title of host publicationSustainable Development of Urban Environment and Building Material
Pages1100-1105
Number of pages6
DOIs
StatePublished - 2012
Event4th International Conference on Technology of Architecture and Structure, ICTAS 2011 - Xi'an, China
Duration: 22 Sep 201124 Sep 2011

Publication series

NameAdvanced Materials Research
Volume374-377
ISSN (Print)1022-6680

Conference

Conference4th International Conference on Technology of Architecture and Structure, ICTAS 2011
Country/TerritoryChina
CityXi'an
Period22/09/1124/09/11

Keywords

  • CFD
  • Commercial kitchen
  • Displacement ventilation
  • IAQ

Fingerprint

Dive into the research topics of 'Numerical study on indoor air quality of commercial kitchen in china'. Together they form a unique fingerprint.