Numerical Simulation of Environmental Control for Relics Preservation in the Funerary Pit by Air Curtain System

Research output: Contribution to journalConference articlepeer-review

4 Scopus citations

Abstract

The air pollution and fluctuation of environmental parameters are the main causes of desiccation cracking, efflorescence of relics in archaeology museum. In this research, an air curtain system was proposed to separate the local environment in funerary pit from the large-space exhibition hall. An investigation of the air curtain was carried out to evaluate the integrated performance and to obtain the optimal jet elevation and velocity of the air curtain. The results show that the optimal jet elevation and jet velocity of the air curtain system were 3° and 5.5m/s, respectively. The preservation environment in the funerary pit can be greatly improved by the air curtain, the temperature difference between the top and bottom of funerary pit could be reduced to only 0.2°C. Moreover, the isolation efficiency of the air curtain system can reach to 89%.

Original languageEnglish
Pages (from-to)265-272
Number of pages8
JournalProcedia Engineering
Volume205
DOIs
StatePublished - 2017
Event10th International Symposium on Heating, Ventilation and Air Conditioning, ISHVAC 2017 - Jinan, China
Duration: 19 Oct 201722 Oct 2017

Keywords

  • Air curtain system
  • Archaeology Museum
  • Relics Preservation

Fingerprint

Dive into the research topics of 'Numerical Simulation of Environmental Control for Relics Preservation in the Funerary Pit by Air Curtain System'. Together they form a unique fingerprint.